Pilz PSENvip RL D P Instrukcja Użytkownika Strona 43

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 139
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 42
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: [email protected]
4-15
4.4 Description of the units
4 Function description
The load must not switch on because of the test.
Testing for shorts
A test is regularly carried out to check for shorts between the outputs.
Fig. 4-8: Test pulses
Key:
t
1
: Pulse length of on test (40 μs)
t
2
: Repetition length of on test (100 μs ... 3 ms)
t
3
: Cycle time of on test (30 μs ... 5 min)
][Funktionsbeschreibung_BA_Zusatz Einschalttest
WARNING!
When wiring an output with capacitance it is essential to note
the pulse duration, repetition period and scan time of the power-
up test, otherwise the load may switch on unintentionally.
1
t
2
t
1
t
1
t
3
t
1
t
t
2
t
1
U
0
Przeglądanie stron 42
1 2 ... 38 39 40 41 42 43 44 45 46 47 48 ... 138 139

Komentarze do niniejszej Instrukcji

Brak uwag