7.1 Messages
7 Operation
77000OperationOperation7-7.1Messages7100Messages7-][BA_Betrieb Störung LED "Err" Sys A + B
A module error is displayed via the "Err" LED (see section entitled "Dis-
play elements"), signalled to the head module and then entered in the
head module's
Error stack, with PSSu in system environment A
Diagnostic log, with PSSu in system environment B.
][BA_Betrieb Fehler ST
The module can detect the following errors:
Module error Explanation Remedy
Start-up error Error as the PSSu system starts up. Change faulty module.
Configuration error Incorrect module type configured. The configured hardware registry does
not match the actual hardware regis-
try.
ST communication error Error in ST communication with the
head module.
Change faulty module.
Bus termination error There is no end bracket. Install a terminating plate with inte-
grated end angle.