Pilz PSSu E S 2DO 2-T Instrukcja Użytkownika Strona 27

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 35
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 26
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: [email protected]
6-3
6.2 Terminal configuration
6 Wiring
6.2Terminal configuration6200Terminal configuration6-][Klemmenbelegung 2DO
Base module Terminal configuration
Screw terminals:
PSSu BP 1/8S
PSSu BP 1/8S-T
Cage clamp terminals:
PSSu BP 1/8C
PSSu BP 1/8C-T
Without C-rail:
11: Output O0
21: Output O1
12-22: 0 V periphery supply
(12-22 linked within the base module)
13-23: 0 V periphery supply
(13-23 linked within the base module)
14: Not connected
24: Not connected
Screw terminals:
PSSu BP-C 1/8S
PSSu BP-C 1/8S-T
Cage clamp terminals:
PSSu BP-C 1/8C
PSSu BP-C 1/8C-T
With C-rail:
11: Output O0
21: Output O1
12-22: 0 V periphery supply
(12-22 linked within the base module)
13-23: C-rail supply
(13-23 linked within the base module)
14: Not connected
24: Not connected
Screw terminals:
PSSu BP-C1 1/12S
PSSu BP-C1 1/12S-T
Cage clamp terminals:
PSSu BP-C1 1/12C
PSSu BP-C1 1/12C-T
With C-rail:
11: Output O0
21: Output O1
12-22: 0 V periphery supply
(12-22 linked within the base module)
13-23: C-rail supply
(13-23-16-26 linked within the base
module)
14: Not connected
24: Not connected
15-25: 0 V periphery supply
(15-25 linked within the base module)
16-26: C-rail supply
(13-23-16-26 linked within the base
module)
2111
2212
2313
2414
2111
2212
2313
2414
2111
2212
2313
2414
2616
2515
Przeglądanie stron 26