7-1
7.1 Messages
7 Operation
77000OperationOperation7-7.1Messages7100Messages7-][BA_Betrieb Störung LED "Err" Sys B
A module error is displayed via the "Err" LED (see section entitled "Dis-
play elements"), signalled to the head module and then entered in the
head module's diagnostic log.
][BA_Betrieb Fehler Ser
The module can detect the following errors:
Errors Statement Remedy
Start-up error Error as the PSSu system starts up Change faulty module.
Configuration error Wrong module type selected or invalid
module configuration
Adjust the configured hardware regis-
try to the actual hardware registry so
that they match, or correct the module
configuration.
ST communication error Error during ST communication Change faulty module
Bus termination error There is no terminating plate or there is
a bad contact with the module bus.
Install a terminating plate with inte-
grated end bracket or insert the base
modules together correctly.