3 Safety
3.1 Intendeduse
ThemodulemaybeusedforfailsafeapplicationsinsystemenvironmentB(automation
systemPSS4000).
ThemodulesPSSuEFAIIandPSSuEFAIITmaybeusedasasafetycomponentin
accordancewiththeLiftsDirective95/16/EC,EN811,EN812andEN1151.
Theprogrammablesafetysystemshouldbeinstalledinaprotectedenvironmentthatmeets
atleasttherequirementsofpollutiondegree2.Example:Protectedinsidespaceorcontrol
cabinetwithprotectionclassIP54andcorrespondingairconditioning.
Themoduleprovidesananalogueinput.
TheanalogueinputmeetstherequirementsofENIEC62061:SILCL2.Toachievehigher
safetyvalues,twoanalogueinputswillneedtobeused.PLe(Cat.4)andSILCL3can
beachievedasaresultofredundantinputdata.
Themoduleguaranteesfunctionalsafety,butnotthesafetyoftheentireprocess.
Pleasenotethefollowingduringconfigurationandwithintheuserprogram:
}
With1channeloperation,checkthefeasibiltyofthemeasuredvaluewithananticip
atedmeasuredvalueinordertodetectmeasurementerrorsandoffseterrorsonthe
sensor,ortodetectopencircuitandshortcircuitbetweensensorandmodule.
}
With1channeloperation,useasensorthatmeetstherequirementsofENIEC62061:
SILCL2.
}
With2channeloperation,checkthefeasibilitybyusingtwoinputsandtwosensors.
Takeappropriatemeasurestoavoidcommoncauseerrorsinthesensortechnology,by
usingdiversesensorsoraseparatesupplyvoltageforthesensors,forexample.
}
Monitoradefinedmeasuringrangetodetectopencircuitorshortcircuit:werecom
mend4…20mA.
Themeasuredvalueisattenuatedthroughtheinputfilter.Atthecutofffrequency,theamp
litudeofthemeasuredvalueis70%oftheamplitudeoftheinputsignal.
Westronglyrecommendtheuseofthefollowingfunctionblocks:
}
FS_AnalogueInputSingle(usingoneinput)
}
FS_AnalogueInputDual(usingtwoinputs)
Thefunctionblockscontain"Feasibilitycheck"(onlyonFS_AnalogueInputDual)and"Limit
valuemonitoring"functions,whichenableyoutodetecterrorsinthesensoraswellasthe
wiring.Forthe"Rangemonitoring"functionwerecommendthatyouuseameasuringrange
of4…20mA.
ThemodulePSSuEFAIITissuitableforusewherethereareincreasedenvironmental
requirements(seeTechnicalDetails).
ThemodulePSSuEFAIIRissuitableforusewherethereareincreasedenvironmental
requirementsdemandedbyrailwayapplications(seeTechnicalDetails).
IntendeduseincludesmakingtheelectricalinstallationEMCcompliant.Pleaserefertothe
guidelinesstatedinthe"PSSuniversalInstallationManual".Themoduleisdesignedforuse
inanindustrialenvironment.Itisnotsuitableforuseinadomesticenvironment,asthiscan
leadtointerference.