9 Application Examples
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: [email protected]
9-2
Safe monitoring with "reduced speed" operating mode
Configuration in the PNOZmulti Configurator
Standstill: depending on requirement
Speed n1: reduced speed, depending on requirement
speed n2: greater than the maximum permitted speed.
If the "Overspeed" output (see red marking) = "0", either the maximum
permitted speed has been exceeded or the speed monitor has recog-
nised a fault.
"Overspeed" output = "0" must lead to the shutdown of the relevant ax-
is, irrespective of whether the "reduced speed" operating mode is ac-
tive.