Safety
OperatingManualPNOZs50
1002194EN02
10
3 Safety
3.1 Intendeduse
ThePWMrelayPNOZs50isdesignedforuseinsafetyrelatedapplications.
ThedevicemeetstherequirementsofENISO138491uptoPLeandENIEC62061upto
SILCL3.Forexample,itisdesignedforusewith
}
Mechanicalholdingbrakes.
}
Valves.
IntendeduseincludesmakingtheelectricalinstallationEMCcompliant.Theproductisde
signedforuseinanindustrialenvironment.Itisnotsuitableforuseinadomesticenviron
ment,asthiscanleadtointerference.
Thefollowingisdeemedimproperuseinparticular:
}
Anycomponent,technicalorelectricalmodificationtotheproduct
}
Useoftheproductoutsidetheareasdescribedinthismanual
}
Useoftheproductoutsidethetechnicaldetails(seechapterentitled“TechnicalDe
tails”)
Pleasenotethefollowingsafetyguidelines:
Hazardanalysis
}
Themachinemanufacturermustproduceahazardanalysisforthemachine.Hemust
takeappropriatemeasurestoensurethatunexpectedmovementsdonotleadtohaz
ardoussituationsforeitherpeopleorequipment.
Demandsonthesafetycontrolsystem
}
ThePNOZs50mayonlybeoperatedinconjunctionwithahigherlevelsafetycontrol
system.
}
Theoutputsonthesafetycontrolsystemusedtoactivatefastshutdownmustbetested
todetectshortsacrosscontactsandearthfaults.
}
ThefaultsignaloutputO3mustbeevaluatedtogetherwithstatusoutputsO4(ifO1+/
O1isused)andO5(ifO2+/O2isused),ifthisisdemandedbytheplant/machine's
safetyrequirements.Processingofthesesignalsisusedtocheckthefeasibilityofthe
signalstates.Evaluationofthesesignalsmustbesuitabletoachieveasafecondition
fortheapplication.
Demandsontheconnected,inductiveload
}
Theinductiveloadmustguaranteethedemandsonthesafetyfunctioninadeener
gisedstate.Forexample,inadeenergisedstateaconnectedsafebrakemustalways
beapplied,muststopahazardousmovementandmustpreventunintendedstartup.
Slowshutdownintheeventofafault
}
Whendesigningasafeapplication,youshouldconsiderthataslowshutdowninstead
ofafastshutdownmaybeeffectiveintheeventofafault.Aconnectedbrakemayhave
alongerstoppingdistance.
Slowshutdown
}
Thepowercircuit'sslowshutdownisnotsafetyrelated.Itmayonlybeusedwhenper
mittedbythehazardanalysis.